Outdoor Air Switches
Selection on Basis of Insulation Level
Table 1 - Insulators
Available Insulators c Post
Ratings, kV
Insulator Technical Reference Number
Notes:
Post
Bolt Circle
Maximum Design
Nominal
BIL
For complete mechanical and electrical characteristics, contact the nearest sales representative.
Standard Strength
High Strength
3"
5"
8.3
7.2
95
202 205 208 210 214 216 286 288 291 304 312 324
222 225 227 231 267 278 287 289 295 308 316 368
8 8 8 8 8 8 8 8 8
8 8 8 8 8 8 8 8 8 8 8
15.5
14.4
110 150 200 250 350 550 650 750 900
27 38
23
d Technical Reference numbers not assigned by NEMA.
34.5
48.3 72.5 123 145 170 245 245 362 550 550 800
46 69
115 138 161 230 230 345 500 500 765
e Not available
e
1050 1300 1550 1800 2050
e e
d d e e
Switch open gap dimensions are selected to provide voltage withstand characteristics that exceed line-to-ground voltage withstand characteristics in order to protect personnel and equipment.
TABLE OF CONTENTS
PAGE
Table 2 - Switch Open Gaps
SELECTION AND APPLICATION Insulator Cantilever Strengths . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Insulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Switch Open Gaps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Ground Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Phase Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Switch Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 INTERRUPTER ATTACHMENTS Arcing Horn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Arc Restrictor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Vacuum Interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Summary of Devices and Ratings . . . . . . . . . . . . . . . . . . . . . . . 7 SWITCH OPERATING MECHANISMS MO-10 Motor Operator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10 Swing Handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Worm Gear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Three-Pole Torsional Control . . . . . . . . . . . . . . . . . . . . . . . . . . .11 ACCESSORIES Grounding Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Cable Guides. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Auxiliary Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 EHV Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Min. (inches) Metal-to-Metal
Ratings, kV
Double Break One End
Single Break
Maximum Design
Nominal
BIL
8.3
7.2
95
7
NA NA NA
15.5
14.4
110 150 200 250 350 550 650 750 900
10 12 18 22 32 50 60 68 84
27 38
23
34.5
12 15 22 32 38 44 50 57 57 66
48.3 72.5 123 145 170 245 245 362 362
46 69
115 138 161 230 230 345 345
1050 1050 1300
104 104 120
Above 362 kV maximum design, switch open gap dimensions are dictated by expected maximum switching surge voltage levels.